Page 279 - Womens Pavilion
P. 279
Oil-Less Claw Medical Vacuum
3.0 Start Up
• Check the electrical cabinet for any broken
components.
• Check that all motor starter connections are
tight and that there are no loose objects such
as terminal lugs, screws, nuts, etc., in the
cabinet.
3.2 Initial Start-up
CAUTION: Complete the prestart-up procedure
before continuing with the initial start-up
procedure
WARNING:
Manual Override
To prevent electrical shock, ensure that Switch
ALL electrical power to the system is OFF, O - On Manual
including the disconnect switches. The
facility’s supply circuit breaker should X - Off
also be locked out. A - Automatic
Figure 3.1 Unit PCB Override Switch
3.2.1 Lubrication Prior to actual operation, the pumps must be
checked for correct rotation.
The pump gears are oil lubricated, but there is
no lubricant or sealing fl uid inside the pumping Inside the control cabinet, switch one of the unit
chamber. printed circuit boards from the manual override
“Off ” position to the bottom position, the default
All LifeLine® Claw vacuum pumps are shipped “Automatic” mode. Make sure the Pump Mode on
with the required amount of oil for start-up. All the Unit touchscreens are in the Off position, see
models are shipped with the required oil already Figures 3.2 and 3.3. (See Figure A.15 for complete
in the pumps. list of Screen Toolbar Descriptions)
3.2.2 Pump Rotation
Inside the control panel, make sure that all unit
printed circuit boards are set to the manual
override “Off ” position. This is indicated by the
middle position “X” on the three-position sliding
switch as shown in Figure 3.1.
Check all voltages supplied to the LifeLine® system
to ensure they are the required value and phases
needed by the control panel.
Apply power to the system and turn the disconnect
switches to “On”.
Figure 3.2 Unit Screen - Off Position
4107 9000 95.04 3-2