Oil-Less Claw Medical Vacuum
3.0 Start Up
Main Screen Unit Screen # 1 Unit Screen # 2
TM
EMBEDDED
Proximity Sensor
Power ON Light
Alarm Buzzer
Figure 3.3 Touchscreen Controls
Direct On Line or Wye Delta Starting
Check for correct direction of rotation of each pump
by pressing the “Rotation” button on touchscreen
display (found in the Service section of the Unit
touchscreens) and observing rotation. See Figure
3.4. The Pump Mode for each compressor must
be in the Off Position for the Rotation to function.
By observing the cooling fan of the motor, you can
determine the rotation of the pump. After pressing
the “Rotation” button on the touchscreen, there
is a 3 second delay before the pump will start for
a brief amount of time. Pump rotation should be Figure 3.4 Unit Screen - Service: Rotation
counterclockwise when looking at the rear of the Variable Speed Drive
motor. Directional arrows are located on each Prior to actual operation, the pumps must be
pump.
checked for correct rotation in both “Manual” and
“Automatic” position. In the “Manual” position,
If the pumps are rotating in the wrong direction,
rotation can be reversed by switching any two the pump starts Across the Line. In the “Automatic”
main power leads to the panel. Correct rotation position, the pump starts with the Variable Speed
should be confi rmed in the previous manner. Drive. It is possible for the pump to turn in one
direction when started in the “Manual” position,
Repeat the process of switching the Unit printed and then turn the other direction when started in
circuit boards from the manual override “Off ” the “Automatic” position. This must be checked
position to the default “Automatic” position and using the following two steps.
testing rotation.
3-3 4107 9000 95.04