TotalAlert Infinity™ NFPA Medical Gas Notification System
• Alarm Type Tab • Initialize Modules Tab
The ALARM TYPE screen defines which type The PRIMARY SETTINGS screen will now dis-
of alarm will be displayed and drives later play with ALARM TYPE checked and INITIAL-
setup functions. IZE MODULES active.
• Touch the INITIALIZE MODULES tab.
Figure 125: Alarm Type Tab
• Touch the ALARM TYPE tab.
• Choose a code style based on code re- Figure 127: Initialize Modules Screen
quirements.
• Touch the COMBO tab. The INITIALIZE MODULES screen is used to set
up the boards that are installed. The boards
function as the input/output hardware of the
alarm.
Save At this point, you have two options:
Erase 1. Either touch the Scan button to prompt
the alarm to autofill the screen for you.
OR
2. Complete the screen by selecting the
boards installed in the alarm.
Figure 126: Choosing Code and Alarm Styles
Touch the Save button when you see checks
• Once the desired tabs are selected, touch beside your selections.
the Save button to save the selection and Notes:
go back to the PRIMARY SETTINGS screen.
1. Select the NFPA/CSA SIGNAL / B1x board
Note: To clear your selections, touch the during the configuration of a combination
Erase button. alarm.
2. Select Gas Input / B60 or Gas Combina-
tion / B65 depending on hardware in-
stalled in the alarm.
4-29 4107 9016 58.02