TotalAlert Infinity™ NFPA Medical Gas Notification System
C = [Gas Name] Tab E = [Units Of Measure] Tab
Figure 116: Gas Text Screen Figure 118: [Units of Measure] Tab
1. Touch the Erase button on the keyboard To change the unit of measure:
to delete the gas name. 1. Touch the tab for the appropriate unit of
2. Enter the new gas name. Touch the [<ÁÑ] measure.
to toggle to symbols. Touch the [1AZ] key 2. Touch the Save button to close the screen
to toggle back to letters and numbers.
F = Low Alarm Settings Tab
3. Touch the Save button.
D = Area Monitored Tab
Figure 119: Low Alarm Settings Tab
Figure 117: Area Monitored
To add locations to be monitored: • Low Alarm Set Point
1. Touch an unused location tab. You can remove the low alarm set point or
customize the low alarm set point.
2. Using the keyboard, enter the name of the
location that you would like to monitor To remove the low alarm set point:
(e.g., ROOM 1). Enter multiple locations 1. Touch the NONE tab.
as needed (e.g., Room 1, Room 2, Room 2. Touch the check on the CONFIRM SET-
5). TINGS CHANGE screen.
3. Touch the Save button. A check appears To customize the low alarm set point:
when the location is saved. 1. Touch the ADJUST tab.
Note: To edit the location information, touch 2. Enter the new set point.
the Pencil button.
3. Touch the Save button.