TotalAlert Infinity™ NFPA Medical Gas Notification System
Eight source signal inputs (B-J) can be tied B2 = Signal Settings Tab
to each location. Two tabs are used for the
detailed configuration of each source signal
input. The two tabs for each source signal
input are paired and named alphabetically
(e.g., B1 and B2 / C1 and C2 / D1 and D2 /
etc.) (Figure 107).
Users can scroll to the first tab for each source
signal input by using the right and left arrows
at the bottom of the screen. To jump quickly
to the second and third screens, simply touch
a letter button on the grid on the left that Figure 110: Signal Settings tab
appears on that screen (e.g., the D button
jumps to the second screen and the G button • Signal Text
jumps to the third screen). Touch the NONE/BLANK tab.
The first tab for each source signal input is
highlighted and the second grayed out to
ensure that users complete the setup in the
correct order. The second tab in each pair
will become available to you as you advance
through setup.
Figure 111: Signal Text Tab
To select source signal input text:
• Scroll through the options using the
right and left arrows at the bottom of the
screen.
• Touch the tab for the appropriate option,
Figure 109: Alarm Point Tab or select a blank to create a custom alarm.
B1 = Alarm Point Tab • Touch the Save button when you see a
To identify the location where the wires are check beside your selection to save the
landed: selection and return to the SIGNAL SET-
1. Touch the B1 tab TINGS screen.
2. Touch the tab for the appropriate board Active Alarm Instruction:
and terminal block. To set facility instructions for active alarms,
3. Touch the Save button when you see a touch either the GENERAL MESSAGE or OP-
check beside your selection to go auto- TION MSG tab. The alarm defaults to GEN-
matically to the SIGNAL SETTINGS screen. ERAL MESSAGE. See Section 4.6 for how to
set up custom instructions.
4-23 4107 9016 58.02