Page 490 - Womens Pavilion
P. 490

TotalAlert Infinity™ NFPA Medical Gas Notification System



            Eight source signal inputs (B-J) can be tied         B2 = Signal Settings Tab
            to each location. Two tabs are used for the
            detailed configuration of each source signal
            input. The two tabs for each source signal
            input are paired and named alphabetically
            (e.g., B1 and B2 / C1 and C2 / D1 and D2 /
            etc.) (Figure 107).

            Users can scroll to the first tab for each source
            signal input by using the right and left arrows
            at the bottom of the screen. To jump quickly
            to the second and third screens, simply touch
            a letter button on the grid on the left that                  Figure 110: Signal Settings tab
            appears on that screen (e.g., the D button
            jumps to the second screen and the G button          •  Signal Text
            jumps to the third screen).                          Touch the NONE/BLANK tab.
            The first tab for each source signal input is
            highlighted and the second grayed out to
            ensure that users complete the setup in the
            correct order. The second tab in each pair
            will become available to you as you advance
            through setup.








                                                                            Figure 111: Signal Text Tab

                                                                 To select source signal input text:
                                                                 •  Scroll through the options using the
                                                                    right and left arrows at the bottom of the
                                                                    screen.
                                                                 •  Touch the tab for the appropriate option,
                      Figure 109: Alarm Point Tab                   or select a blank to create a custom alarm.

            B1 = Alarm Point Tab                                 •  Touch the Save button when you see a
            To identify the location where the wires are            check beside your selection to save the
            landed:                                                 selection and return to the SIGNAL SET-
            1.  Touch the B1 tab                                    TINGS screen.

            2.  Touch the tab for the appropriate board           Active Alarm Instruction:
               and terminal block.                                To set facility instructions for active alarms,

            3.  Touch the Save button when you see a              touch either the GENERAL MESSAGE or OP-
               check beside your selection to go auto-            TION MSG tab. The alarm defaults to GEN-
               matically to the SIGNAL SETTINGS screen.           ERAL MESSAGE. See Section 4.6 for how to
                                                                  set up custom instructions.