TotalAlert Infinity™ NFPA Medical Gas Notification System



                                                               4.5.1 Configuring Source Badges
           NOTE:
                                                                                       ™
           See the end of this section for information         The TotalAlert Infinity  combination alarm
           on the Miscellaneous Tab. See section 4.6           is designed to allow the configuration of ten
           for information on the Active Alarm Opt             source badges. Twenty locations with up to
           Tab.                                                eight source signals each can be tied to each
                                                               source badge.
           4.5 Setting up a Combination Alarm
                                                               To configure alarm points in a master badge,
                                                               touch the [1] button on the configuration
                                                               screen (Figure 101).



















                                                                    Figure 100: Combination Alarm Screen
            Figure 99: Combination Alarm User Interface
                                                                •  Configure (Source) Screen
           The TotalAlert Infinity  combination alarm           Ten gases (A-K) can be tied to master badges.
                                  ™
           combines the functionality of an area alarm
           and a master alarm. It monitors two things:          Three tabs are used for the configuration of
                                                                each source badge (Figure 102).
           •  Gases and their pressures.
           •  Source equipment.                                 1 = GAS COLOR           To change color codes
                                                                CODE                    based on standard and
           Two independent hard wired alarms monitor-                                   country
           ing source equipment are required per facility
           to meet the 24-hour monitoring requirement           2 = GAS TEXT            To label the gas
           in the NFPA 99 standard.                             3 = LOCATIONS           To add a location for
                                                                                        the source signal




















                                                                      Figure 101: Configure Source Screen


           4107 9016 58.02                                 4-20