TotalAlert Infinity™ NFPA Medical Gas Notification System
A3 = Locations Tab
To select the number of locations to be moni-
tored for this particular gas:
1. Touch the LOCATIONS tab.
2. Use the [+] and [-] buttons to increase and
decrease the number of locations.
3. Touch the 01 button to go automatically
to the CONFIGURE (SOURCE) : 02 screen
Figure 108: [Location] Tab
On the SOURCE LOCATION screen:
1. Touch the 01 tab.
2. Using the keyboard, enter the name of the
location for the source equipment being
monitored (e.g., ROOM 1). Enter multiple
locations as needed (e.g., Manifold Room,
Roof Top, Source Room).
Figure 106: Locations Tab 3. Touch the Save button. A check appears
when the location is saved. Note: To edit
• Configure (Source): 02 Screen
the location, touch the Pencil button.
4. Touch the X button to close and return to
the CONFIGURE (SOURCE) screen.
Figure 107: Configure Source Screen
A = [Location] Tab
To name the location, touch the A = [LOCA-
TION] button.