TotalAlert Infinity™ NFPA Medical Gas Notification System
H = Zero Offset Tab
Active Alarm Instruction:
To set facility instructions for active alarms,
touch either the GENERAL MESSAGE or OP-
TION MSG tab. The alarm defaults to GEN-
ERAL MESSAGE. See Section 4.6 for how to
set up custom instructions.
G = High Alarm Settings Tab
Figure 121: Zero Offset Tab
In some cases, facility dial gauges may show
slightly different readings than the TotalAlert
alarm (e.g., 46 PSI versus 44 PSI). To match
the TotalAlert alarm exactly to a facility dial
gauge:
1. Select the offset amount.
Figure 120: High Alarm Settings Tab
2. Touch the Save button to close the screen.
You can remove the high alarm set point or
customize the high alarm set point. Configuring Additional Area Badges
To remove the high alarm set point: Configure additional area badges by touching
1. Touch the NONE tab. the number on the numeric display that cor-
2. Touch the check on the CONFIRM SET- responds with the area badge and repeating
TINGS CHANGE screen. the steps listed above.
To customize the high alarm set point:
1. Touch the ADJUST tab.
2. Enter the new set point.
3. Touch the Save button.