Page 74 - Gefran - Inverter system and power supply unit (ADV200 Drive family)
P. 74
74 Inverter System & Power Supply Unit
Overload In K1 K2 OT
Sizes
180 % x In
150 % x In
ADV100 ( 1’ each 5‘ ) ( 0,5" each 5‘ )
[a] [a] [a] [%] [%] [°C]
1040 14.3 17.1 9.5 100 3 78
ADV200 - 4 • Basic
...480V Power supply
1055 19.5 23.4 13 100 3 80
2075 24.8 29.7 16.5 100 3 80
2110 34.5 41.4 23 100 3 85
3150 46.5 55.8 31 100 5 92
3185 57 68.4 38 100 5 85
3220 69 82.8 46 100 3 87
4300 93 111.6 62 100 3 87
4370 112.5 135 75 100 3 88
4450 130.5 156.6 87 100 3 90
5550 157.5 189 105 100 3 85
5750 225 270 150 100 5 90
5900 270 324 180 100 5 93
Current limits positions according to output frequency
200
180 FAST current limit
160
ADV100 • 230V
SLOW current limit
140 K3
I out [%] 120 RATED current limit
100
80
K2
60
K1
40
20
0
0 1 2 3 4 5 6 7 8 9 10
_ _ Islow, .... Ifast; __ In f out [Hz]
• k1 indicates the direct current (as a percentage with respect to the rated current) that the drive can deliver at a frequency of 0 Hz.
• k2 indicates the frequency at which the drive can deliver the 150% limit. Between 0 Hz and k2 the limit follows a linear pattern and thus also determines the k3
frequency at which the drive can deliver the 180% limit.
• OT (Drive overload temperature limit) below this temperature the 150% FAST current limit is also enabled for frequencies lower than k2; above this tempera-
ture only the slow current limit is enabled and this varies according to the output frequency and the ambient temperature (max 50°C).
The active current limit is always FAST; if fast I2t is loaded, the active current limit is SLOW. If SLOW I2t is loaded the active current limit is RATED.