Page 516 - Mechatronics with Experiments
P. 516

JWST499-Cetinkunt
            JWST499-c07
                       502   MECHATRONICS  Printer: Yet to Come                      October 9, 2014 8:41 254mm×178mm
                              Let us assume that the supply pressure is constant. When the load pressure is constant, the
                              flow rate is linearly proportional to the current in the solenoid. Similarly, for a constant
                              solenoid current (equivalently a constant spool orifice opening), the flow rate is related
                              to the load pressure with a square root relationship. As the load pressure increases, the
                              available pressure drop across the valve decreases and hence the flow rate decreases. When
                              the load pressure is the same as the tank pressure, all of the supply pressure is lost across
                              the valve and maximum flow rate is achieved, which is called the no-load flow. However,
                              the flow at the output of the valve has no pressure to exert force or torque to the actuator
                              (cylinder or rotary hydraulic motor). Therefore, in a good design, part of the supply pressure
                              is used to support the necessary flow rate across the valve, and part of it is used to provide
                              a load pressure to generate actuator force/torque,
                                                        P − P =ΔP  valve  +ΔP l                 (7.252)
                                                         s
                                                             t
                                   In practice, a valve flow rating (Q ) is given at a standard pressure drop across the
                                                              r
                              valve (ΔP = 1000 psi for servo valves and 150 psi for proportional valves) when the spool
                                      r
                              is fully shifted. The flow rate of the valve (Q) for a different pressure drop (ΔP valve ) across
                              the valve when the spool is fully shifted can be obtained approximately by
                                                               √
                                                        Q = Q ⋅  ΔP valve ∕ΔP r                 (7.253)
                                                             r
                              For valve measurements, P and P are set to constant values, and pressure drop is set
                                                          t
                                                    s
                              to a number of discrete values (Figure 7.75). For each value of the load pressure (ΔP ),
                                                                                                   L
                              current (i) is varied from zero to maximum value (i max ), and flow rate (Q) is measured.
                              The results are plotted as valve flow rate, load pressure, and current relationship as shown
                              in Figure 7.76 for a fixed P and P values. In Figure 7.76, the valve deadband is clearly
                                                    s
                                                          t
                              observed.
                                   The flow–current–pressure relationship given above neglects the leakage flow in the
                              valve. Servo and proportional valves used in precise positioning applications generally


                                 25
                                        P - A   B - T   Direction of flow  P - B   A - T
                                                                     10 bar
                                       P-A                                    P-B
                                Flow rate (in  /s)  15  B-T                     A-T
                                 20
                               3                                     5 bar




                                 10    P-A                                   P-B
                                     B-T                                        A-T
                                 5


                                  0
                                 –2.5 –2.0 –1.5  –1.0  –0.5  0  0.5  1.0  1.5  2.0  2.5
                                               Input signal: solenoid current (Amp)
                              FIGURE 7.76: Valve flow rate versus solenoid current for different pressure drops across
                              ports. A four-way proportional directional valve is considered for different pressure drop
                              values. Servo valves have much smaller deadband and the flow rate-current relationship for a
                              constant pressure drop is more linear compared to those of proportional valves.
   511   512   513   514   515   516   517   518   519   520   521