Configuring a Monitor



































                                            Figure 7-5 Sample ASIM/DSIM Settings
                          Press  the  ‘ASIM/DSIM’  button  in  the  ribbon.    To  configure  one  of  the  Operating
                       Conditions, select the appropriate tab along the left side of the workspace, and then enter
                       the configuration data:
                          •  Select the unit that the Operating Condition is reading; for example, Power can be
                              read in W, kW MW or hp.  The Operating Condition can be disabled here as well.
                          •  Enter the Ethernet information.  The IP address is the address of either the Modbus
                              system or the address programmed into the Remote I/O Module.  The default port
                              number and timeout values do not likely need to be changed.

                          •  Enter the Modbus register settings.  When interfacing to an existing Modbus system,
                              this is provided by the plant.  When interfacing to a Remote I/O Module, the correct
                              settings are based on the Remote I/O Module assembly.
                          •  Enter the translation formula that converts the value read from the Modbus register
                              address into a real-world value.
                          For the ambient temperature and humidity Operating Conditions, there is a checkbox to
                       indicate if they are being acquired from an ambient sensor connected directly to the monitor
                       instead of a Modbus source.