Configuring a Monitor



                          Pressing the “Defaults’ button will set these values based on the asset properties:

                          •  Minimum ‘Full’ load is set to 80% of the rated load
                          •  Maximum ‘Reduced’ is set to 50% of the rated load
                          •  Minimum ‘Hot’ is set to 80% of the rated temperature

                          •  Maximum ‘Cold’ is set to 70% of the rated temperature
































                                             Figure 7-9 Operating Point Settings

              7.4.4.  GuardII+ EV Shaft Trigger Configuration

                          A Shaft Trigger is option for EV measurements on the GuardII+.  Press the ‘Shaft Trigger
                       Setup’ button on the ribbon to configure the shaft trigger.  The shaft trigger configuration is
                       split up into 3 main areas:
                          •  The Synchronization Signal graph shows the shaft trigger signal after it has been
                              detected by the hardware.
                          •  The Shaft Trigger Signal graph shows the raw shaft trigger data and the selected
                              trigger threshold.
                          •  The controls are used to manually acquire a fresh set of shaft trigger data and show
                              some analysis results of the shaft trigger signal.