Page 68 - GuardII+ Series 4208 Platform Flux User Manual
P. 68

Appendix




                                     NOTE:
                                     If the measurement status is consistently showing a value other than “2”,
                                     this  may  indicate  a  problem.    Refer  to  Section  7  for  troubleshooting
                                     instructions and/or consult Iris Power LP Technical Support for assistance.

                        For round-rotor machines, coils with more than 10 turns per coil typically show signs of a
                     problem when the coil-to-coil flux density differs by 3%.  Round-rotor machine coils with less
                     than 10 turns per coil typically show signs of a problem when the coil-to-coil flux density differs
                     by 5% to 10%.  For salient-pole machines, poles typically show signs of a problem when the
                                                                                               th
                     pole-to-pole flux density differs by 1% to 2%.  Flux density is reported in 100 ’s of a percent;
                     so a value of -300 reported on Modbus on a salient-pole machine indicates a flux density drop
                     of 3%, and therefore a potential problem.

              8.4.  Modbus Slave Timing

                                       NOTE:
                                       As  described  in  Section  4.2,  GuardII+  updates  the  flux  Modbus  data
                                       registers after every measurement cycle, which occurs every 30 minutes.;
                                       so while the monitor can respond to Modbus requests very quickly, the
                                       flux data simply will not change that often.  Polling the monitor every few
                                       seconds is just wasting network bandwidth.
                                      Each monitoring technology in the GuardII+ Series 4208 Platform has its
                                       own  measurement  cycle;  so  If  the  monitor  has  other  monitoring
                                       technologies  installed,  those  other  technologies  may  provide  Modbus
                                       updates more rapidly.

                        To  achieve  the  best  performance  when  polling  GuardII+’s  Modbus  data  registers,  the
                     following configurations of the polling system should be used:
                        •  Modbus response timeout should be set to no less than 6000ms

                        •  Modbus polling should occur no more often than once per minute.

              8.5.  Using PLC-Style Addressing

                        GuardII+  uses  protocol-style  Modbus  addressing  (Base  0),  not  PLC-style  Modbus
                     addressing  (Base  1).    When  using  PLC-style  addressing  to  acquire  Modbus  data  from
                     GuardII+, this will cause an address shift.
                                     NOTE:
                                     When accessing GuardII+ data registers using PLC-style addressing, the
                                     address must be increased by 1.


                       Sample Addresses using Modbus (Base 0) Addressing
                       Address           Data                 Notes
                       6000              Year                 The year of the last measurement
                                                                 Expressed in 4 digits (i.e., 2019)




                                                              62
                                                                                          www.irispower.com
   63   64   65   66   67   68   69   70