Page 63 - GuardII+ Series 4208 Platform User Manual
P. 63

Troubleshooting



                        •  If this connection fails, contact Iris Power LP Technical Support for assistance.

              7.10. Alert Relay

                        There are three main components that can cause problems in the Alert Relay; the relay
                     itself, the relay fuse, and the connections to the rest of the system.

                                     WARNING:
                                     Depending on the specific application, there could be up to 250 Vac or 250
                                     Vdc present on the Alert connection.
                                     When  troubleshooting  the  GuardII+  Alert,  take  appropriate  cautions  to
                                    prevent injury due to the voltage levels that may be present.  Disconnect
                                     the Alert source from the monitor whenever possible.


























                                              Figure 7-15 Alert Relay Connection

                                     NOTE:
                                     The troubleshooting process may find a problem with the connection to
                                     the plant system; resolving this may not fall within Iris Power LP’s scope
                                     of responsibility.

                        When the Alert Relay is not functioning or there is an incorrect Alert indication at the plant
                     system, check the following:

                        •  Check that the Alert Relay terminal block is fully inserted and secure.
                        •  Check that the leads connecting to the Alert Relay terminal block are fully inserted and
                            the screws tightened.
                        •  Use a screwdriver to remove FUSE3 and check it.  Replace the fuse if necessary; refer
                            to Section 3.1 for fuse specifications.
                        •  If any of the above were incorrect, check to see if the problem has been fixed.