Page 37 - GuardII+ Series 4208 Platform PD User Manual
P. 37

Installation



              5.  Installation


                        This manual only describes installation of the PD card itself; for details on the installation
                     of the GuardII+ Series 4208 Platform assembly or PD sensors, refer to the appropriate User
                     Manual for that component.
                        This installation procedure assumes that no other monitoring technologies are installed in
                     the GuardII+ monitor.  Note that if there is another monitoring technology, this will not affect
                     the installation of the PD card, however care must be taken to make sure the card and cabling
                     for the other technology are not disturbed.
                                    NOTE:
                                    GuardII+ installation must be performed by qualified personnel according
                                    to all applicable local regulations and standards.

                                    Use the monitor only as specified by the operating instructions or the safety
                                     protection of the monitor may be impaired.

                                    NOTE:
                                    The information provided represents a typical installation for a GuardII+
                                    PD card.  Some installations may require custom work not described here;
                                    if  assistance  is  needed  contact  Iris  Power  LP  Technical  Support.    For
                                     installation of specific monitoring technologies refer to the User Manual for
                                    that technology.


              5.1.  Overview

                        The installation shall be performed according to this manual and applicable local codes
                     and standards.

                        For valid monitor operation, the GuardII+ should only be connected to Iris Power LP PD
                     sensors or Iris Power LP approved equivalents.

                                    WARNING:
                                    Before working with the GuardII+ monitor, disconnect the power.  This
                                    can be done at the plant breaker or the power switch inside the monitor.
                                    A circuit breaker must be near the equipment and it shall be marked as the
                                    disconnecting device for the equipment.  The maximum rating of the circuit

                                    breaker is 15 AMP.  If the monitor needs to be removed from the enclosure,
                                    use the plant breaker to disconnect the power.

                                    IMPORTANT:
                                    The main power source for the GuardII+ should NOT be a line on which
                                    severe voltage dips or voltage drop-outs may occur.  These may cause
                                     problems for the monitor.

                                    NOTE:
                                    Remove the electronics from the enclosure before drilling conduit holes.
                                    Refer to the GuardII+ Series 4208 Platform User Manual for details.