PD Card Operation
4.7. Modbus Outputs
PD Measurement data is hosted inside the monitor for an external Modbus master to read.
To access the data registers, connect to the GuardII+ using Ethernet and query the monitor
using the standard Modbus over TCP/IP protocol. This data is updated during every
measurement cycle. Modbus data outputs include (for each combination of input and range):
• Measurement time
• Measurement status
• Summary numbers
• 2D data
• Modbus data outputs do not include raw data.
• Alert status
Refer to Section 8.2 for the list of Modbus PD register addresses.
4.8. GuardII+ Alerts
Alerts in a GuardII+ PD system are based on the Very High Qm threshold configured in
IAM; when any measurement produces Qm results higher than the Very High threshold for 4
consecutive measurement cycles, the Alert is asserted.
NOTE:
There are two configurations that need to be completed using IAM for the
Alert feature to function fully:
• First, there is a general Alert Relay behavior that must be set to a
selection other than ‘Disabled’; if the Alert Relay behavior is not
configured, then the Alert Relay will not function, although Archived
measurements and Modbus data will still report an Alert when it
occurs.
• Second, the Very High threshold must be set.
Refer to Section 6.3 for details on GuardII+ configuration.
NOTE:
One recommended use of the User Defined Trigger is to capture additional
data once an Alert has occurred; the Alert is an indicator that PD levels
have reached a point to cause concern, so some more frequent data
collection is a good idea.