Page 32 - GuardII+ Series 4208 Platform PD User Manual
P. 32

PD Card Operation



              4.7.  Modbus Outputs

                        PD Measurement data is hosted inside the monitor for an external Modbus master to read.
                     To access the data registers, connect to the GuardII+ using Ethernet and query the monitor
                     using  the  standard  Modbus  over  TCP/IP  protocol.    This  data  is  updated  during  every
                     measurement cycle.  Modbus data outputs include (for each combination of input and range):
                        •  Measurement time

                        •  Measurement status
                        •  Summary numbers
                        •  2D data

                        •  Modbus data outputs do not include raw data.
                        •  Alert status

                        Refer to Section 8.2 for the list of Modbus PD register addresses.

              4.8.  GuardII+ Alerts

                        Alerts in a GuardII+ PD system are based on the Very High Qm threshold configured in
                     IAM; when any measurement produces Qm results higher than the Very High threshold for 4
                     consecutive measurement cycles, the Alert is asserted.
                                     NOTE:
                                     There are two configurations that need to be completed using IAM for the
                                     Alert feature to function fully:

                                       •  First, there is a general Alert Relay behavior that must be set to a
                                           selection  other  than  ‘Disabled’;  if  the  Alert  Relay  behavior  is  not
                                           configured, then the Alert Relay will not function, although Archived
                                           measurements  and  Modbus  data  will  still  report  an  Alert  when  it
                                           occurs.

                                       •  Second, the Very High threshold must be set.

                                     Refer to Section 6.3 for details on GuardII+ configuration.

                                     NOTE:
                                     One recommended use of the User Defined Trigger is to capture additional
                                     data once an Alert has occurred; the Alert is an indicator that PD levels
                                     have  reached  a  point  to  cause  concern,  so  some  more  frequent  data
                                     collection is a good idea.