Page 23 - 14th @ Irving Basis of Design (internal)
P. 23
3.2.2 INDOOR DESIGN CONDITIONS
Space Summer Winter
(no humidification)
Office 74°F/50% (±2°F; ±5%RH) 72°F ±2°F
Retail 74°F/50% (±2°F; ±5%RH) 72°F ±2°F
Main Lobby 74°F/50% (±2°F; ±5%RH) 72°F ±2°F
Core Toilet 74°F 72°F
Locker Rooms 74°F 72°F
Electric Rooms 10°F Above Ambient 60°F
Elevator Machine 85°F 65°F
Rooms
Service and Storage Ambient + 10°F DB° 60°F
Areas
Gas Meter Room Natural Ventilation 68°F
Min 12” x 12” louver
Loading Dock Exhaust only 50°F
Mechanical Rooms Ventilation only for major 68°F
equipment spaces.
14th @ IRVING WSP
Project No. B1809809.000
RAL COMPANIES & AFFILIATES Page 23