3.2.2  INDOOR DESIGN CONDITIONS


                                       Space                  Summer                  Winter
                                                                                 (no humidification)

                                Office                74°F/50% (±2°F; ±5%RH)    72°F ±2°F

                                Retail                74°F/50% (±2°F; ±5%RH)    72°F  ±2°F

                                Main Lobby            74°F/50% (±2°F; ±5%RH)    72°F  ±2°F

                                Core Toilet           74°F                      72°F

                                Locker Rooms          74°F                      72°F
                                Electric Rooms        10°F Above Ambient        60°F

                                Elevator Machine      85°F                      65°F
                                Rooms

                                Service and Storage   Ambient + 10°F DB°        60°F
                                Areas

                                Gas Meter Room        Natural Ventilation       68°F
                                                      Min 12” x 12” louver

                                Loading Dock          Exhaust only              50°F

                                Mechanical Rooms      Ventilation only for major  68°F
                                                      equipment spaces.