Page 25 - 14th @ Irving Basis of Design (internal)
P. 25
3.2.5 LOAD DENSITIES (HEAT REJECTION RATE) FOR COOLING
Lighting Equipment Total
Area
(w/sf) (w/sf) (w/sf)
General Office Space 1.1 3.9 5
Retail Areas 1.7 8.3 10
Lobby 1.3 3.9 5.2
3.2.6 ACOUSTIC CRITERIA: (TO BE REVIEWED BY ACOUSTICAL CONSULTANT)
Occupancy NC rating
Occupied Spaces NC 40
Lobbies NC 40
Mechanical Spaces NC 50
3.2.7 FILTRATION CRITERIA
Occupancy Air Filtration Requirements
Occupied Spaces MERV 13
MEP Spaces No filters
3.2.8 THERMAL ZONING
1. Each floor will be served by multiple air-cooled VRF systems with heat recovery capability. Each system will consist of outdoor
units, indoor units, branch circuit controllers and the refrigerant distribution system.