3.2.5  LOAD DENSITIES (HEAT REJECTION RATE) FOR COOLING

                                                    Lighting          Equipment              Total
                               Area
                                                     (w/sf)             (w/sf)               (w/sf)

                      General Office Space            1.1                3.9                   5

                      Retail Areas                    1.7                8.3                  10

                      Lobby                           1.3                3.9                  5.2




        3.2.6  ACOUSTIC CRITERIA: (TO BE REVIEWED BY ACOUSTICAL CONSULTANT)
                                 Occupancy                                NC rating

                                 Occupied Spaces                            NC 40

                                 Lobbies                                    NC 40

                                 Mechanical Spaces                          NC 50



        3.2.7  FILTRATION CRITERIA

                                Occupancy                   Air Filtration Requirements

                                Occupied Spaces             MERV 13

                                MEP Spaces                  No filters



        3.2.8  THERMAL ZONING

        1.  Each floor will be served by multiple air-cooled VRF systems with heat recovery capability. Each system will consist of outdoor
            units, indoor units, branch circuit controllers and the refrigerant distribution system.