Page 25 - 14th @ Irving Basis of Design (internal)
        P. 25
     3.2.5  LOAD DENSITIES (HEAT REJECTION RATE) FOR COOLING
                                                    Lighting          Equipment              Total
                               Area
                                                     (w/sf)             (w/sf)               (w/sf)
                      General Office Space            1.1                3.9                   5
                      Retail Areas                    1.7                8.3                  10
                      Lobby                           1.3                3.9                  5.2
        3.2.6  ACOUSTIC CRITERIA: (TO BE REVIEWED BY ACOUSTICAL CONSULTANT)
                                 Occupancy                                NC rating
                                 Occupied Spaces                            NC 40
                                 Lobbies                                    NC 40
                                 Mechanical Spaces                          NC 50
        3.2.7  FILTRATION CRITERIA
                                Occupancy                   Air Filtration Requirements
                                Occupied Spaces             MERV 13
                                MEP Spaces                  No filters
        3.2.8  THERMAL ZONING
        1.  Each floor will be served by multiple air-cooled VRF systems with heat recovery capability. Each system will consist of outdoor
            units, indoor units, branch circuit controllers and the refrigerant distribution system.
        14th @ IRVING                                                                                             WSP
        Project No.  B1809809.000
        RAL COMPANIES & AFFILIATES                                                                             Page 25





