3.2.3  OUTSIDE AIR VENTILATION AND OCCUPANCY RATES

                          Occupancy                   Ventilation                   Occupancy Density
                         Classification                                                per 1000 ft 2
                                            CFM/Person           CFM/s.f.

                      Offices                    5                 0.06                     5

                      Conference Rooms           5                 0.06                    50
                      Lobby                      -                 0.06                     -

                      Retail Sales
                      (Through retail           7.5                0.12                    15
                      louvers)
                      Retail Storage
                      (Through retail            -                 0.12                     -
                      louvers)
                                                10                 0.12                    35
                      Classrooms
                      Back of the house          -                 0.5                      -

                                                               Temperature
                      MER Rooms                  -                                          -
                                                                 control

                      Storage Rooms              -                 0.5                      -




        3.2.4  EXHAUST RATES

                             Service                                     Exhaust Rates


                      Office Toilet                 50 CFM per toilet fixture
                      Retail Toilet                 50 CFM per toilet fixture via retail louvers

                      Shower Rooms                  50 CFM / shower head

                      Fuel Oil Tank Room            3 air changes

                      Commercial Kitchen            Total of 10,000 CFM for food court

                      Trash Room                    6 air changes

                      Post-fire Smoke Purge         Minimum 6 air changes