     3.2.3  OUTSIDE AIR VENTILATION AND OCCUPANCY RATES
                          Occupancy                   Ventilation                   Occupancy Density
                         Classification                                                per 1000 ft 2
                                            CFM/Person           CFM/s.f.
                      Offices                    5                 0.06                     5
                      Conference Rooms           5                 0.06                    50
                      Lobby                      -                 0.06                     -
                      Retail Sales
                      (Through retail           7.5                0.12                    15
                      louvers)
                      Retail Storage
                      (Through retail            -                 0.12                     -
                      louvers)
                                                10                 0.12                    35
                      Classrooms
                      Back of the house          -                 0.5                      -
                                                               Temperature
                      MER Rooms                  -                                          -
                                                                 control
                      Storage Rooms              -                 0.5                      -
        3.2.4  EXHAUST RATES
                             Service                                     Exhaust Rates
                      Office Toilet                 50 CFM per toilet fixture
                      Retail Toilet                 50 CFM per toilet fixture via retail louvers
                      Shower Rooms                  50 CFM / shower head
                      Fuel Oil Tank Room            3 air changes
                      Commercial Kitchen            Total of 10,000 CFM for food court
                      Trash Room                    6 air changes
                      Post-fire Smoke Purge         Minimum 6 air changes