IDF ROOMS (IDF)
Suspended Ceiling None. Ceiling slab sealant-finished to reduce dust.
Raised Floor None.
Floor Finish Static dissipative coating/sealant
Floor Loading 150 Lbs./ 1 square foot
Door 3’ X 8’ door, outward opening, card access controlled.
Temperature Range (ºF) 68-75
Humidity Range (Relative) Equal to the surrounding area (corridor)
Equipment Power 50 Watts/Sq. Ft.
Convenience Power 120VAC quad outlets at 8’ intervals along on each wall
Power Panels Dedicated.
Fire Suppression Dry pipe pre-action sprinklers
Support Hardware Basket tray runways, 4” X 12” wall mounted and trapeze suspended
from ceiling slab at 8’ AFF
Grounding Secondary Bonding Busbar location
¼” X 4” X 12” way copper bar on insulated standoffs, wall mounted
in the each TSEF