Page 50 - 14th @ Irving Basis of Design (internal)
P. 50

IDF ROOMS (IDF)

              Suspended Ceiling                      None.  Ceiling slab sealant-finished to reduce dust.

              Raised Floor                           None.

              Floor Finish                           Static dissipative coating/sealant

              Floor Loading                          150 Lbs./ 1 square foot

              Door                                   3’ X 8’ door, outward opening, card access controlled.

              Temperature Range (ºF)                 68-75

              Humidity Range (Relative)              Equal to the surrounding area (corridor)

              Equipment Power                        50 Watts/Sq. Ft.

              Convenience Power                      120VAC quad outlets at 8’ intervals along on each wall

              Power Panels                           Dedicated.

              Fire Suppression                       Dry pipe pre-action sprinklers

              Support Hardware                       Basket tray runways, 4” X 12” wall mounted and trapeze suspended
                                                     from ceiling slab at 8’ AFF

              Grounding                              Secondary Bonding Busbar location
                                                     ¼” X 4” X 12” way copper bar on insulated standoffs, wall mounted
                                                     in the each TSEF





































        14th @ IRVING                                                                                             WSP
        Project No.  B1809809.000
        RAL COMPANIES & AFFILIATES                                                                             Page 50
   45   46   47   48   49   50   51   52   53   54   55