Page 48 - 14th @ Irving Basis of Design (internal)
P. 48

The MTER Room shall be located on the basement level and be collocated with the TSER, containing a combination of carrier
        service provider equipment, base building headend/core equipment.

        Conduits shall connect the MTER to the primary Telecommunications Room (TR) riser stack and secondary riser stack.
        The base building network core shall be provisioned with UPS power and emergency stand by power if available.
        Carrier fiber will extend from the TSER to the MTER to provide connectivity to the Wide Area Network/Internet.
        Fiber optic backbone cabling will run from the MTER to every floor in the Tower riser stack for base building network connectivity.


               MAIN TELECOMMUNICATIONS EQUIPMENT ROOM (MTER)

               Location, number                       Basement Level

               Description                            360 Square Feet when collocated with the TSER – 280 sq ft will be
                                                      solely dedicated to the MTER.
                                                      Security cage partition shall divide the MTER from the TSER and
                                                      separate entrances shall be provided to each space.
                                                      The room shall serve the purposes of housing the network core and
                                                      security head end systems.

               Finishes                               4’ X 8’ X ¾” sheets of Fire-Retardant plywood, wall mounted at 6”
                                                      AFF on designated walls, painted white.

               Lighting                               LED 24” X 48” pendants hung at min. 9’ AFF to provide 50 foot-
                                                      candles measured at 3’ AFF

               Suspended Ceiling                      None.  Ceiling slab sealant-finished to reduce dust.
               Raised Floor                           None

               Floor Finish                           Static dissipative coating/sealant
               Floor Loading                          150 Lbs./ 1 square foot

               Door                                   3’ X 8’ outward opening, card access controlled.
               Temperature Range (ºF)                 68-75

               Humidity Range (Relative)              45-55% RH
               Equipment Power                        250 Watts/Sq. Ft.

               Convenience Power                      120VAC quad outlets at 8’ intervals along on each wall
               Power Panels                           Dedicated

               Fire Suppression                       Self-contained mixed gas fire-suppression system such as Victaulic
                                                      Vortex 500 system.

               Support Hardware                       Modular wire-mesh cable tray system sized minimally to 18” X 4”
                                                      and suspended from the structural ceiling with threaded rod.

               Grounding                              Primary Bonding Busbar location
                                                      ¼” X 4” X 20” way copper bar on insulated standoffs, wall mounted
                                                      in the MTER