8.8  TELECOMMUNICATIONS ROOMS (TR)

        The Telecommunications Rooms (TRs) are defined as the interface between the backbone cabling system and the horizontal cabling
        system. The TRs, located on each floor, provide space for backbone and horizontal cable terminations, patching and cross-connect
        equipment, LAN/WLAN electronics and interfaces between the cabling backbone, transport electronics and end user devices.
        The placement of TRs is ultimately dictated by the criteria established under the TIA 568C standard which limits horizontal
        communications cabling to a distance limitation of 295 feet, installed and terminated. WSP recommends that design considerations
        shall limit this figure to a limit of 250 linear feet to account for real-world installation conditions and vertical and horizontal bends.
        TRs shall stack and share same vertical stack of closets with the electrical rooms.  A TR shall be dedicated to serve the floor it is on,
        with the exception being where it is also housing an amplifier unit for a DAS repeater system.

        This will be the means of transporting base building backbone and tenant carrier services backbone cabling throughout the
        building.
        The TR’s will be arranged to accommodate the following systems and equipment:

            •   Termination and patching facilities for horizontal cabling
            •   Termination and patching facilities for voice, data and video backbone cabling
            •   Hardware and racking for LAN cabling switches, VoIP switches, video cabling hubs, converters, and other device sharing
               equipment
            •   Wireless LAN networking equipment
            •   Building Management Systems

            •   Security Systems
            •   CATV equipment
            •   Vertical riser pathways
        Power outlets for any transmission and terminal equipment located within the TR shall be fed from an electrical panel dedicated to
        these loads, ideally located within each TR.
        Panels serving the TR’s shall be on the building UPS/emergency power distribution system.

        Dedicated cooling, electrical and fire suppression provisions are recommended for the TRs, to allow the network and associated
        electronics to operate efficiently and reliably over the life cycle of the building.
        The installation shall be in accordance with TIA 569A. The following are recommended guidelines for the TR’s:

              IDF ROOMS (IDF)


              Location, number                       Every floor

              Description                            80 Square Feet at 8’W X 10’D
                                                     Houses base building and DAS network equipment (if applicable) and
                                                     pathways in addition to pathways for tenant network access.
                                                     Provides carrier point of presence for tenant accommodation
                                                     interconnection.

              Finishes                               4’ X 8’ X ¾” sheets of Fire-Retardant plywood, wall mounted at 6”
                                                     AFF on designated walls, painted white.

              Lighting                               LED 24” X 48” pendants hung at min. 9’ AFF to provide 50 foot-
                                                     candles measured at 3’ AFF