Page 39 - B8773-AEW-XX-XX-PP-A-0001_[P8]_Contractors Manual
P. 39

2.5.3 Timber Ceiling Beams
          102 x 50mm engineered timber ceiling beams
          will be installed in random spacings to match the
          setting out of the 102mm timber wall planks as
          noted on the project drawings. The dimensions
          and  setting  out  of  the  ceiling  beams  will  be
          annotated on the project drawings and should
          also follow these rules;
          1.  The  bottom  of  the  beams  must  never  be
             lower  than  2250mm,  If  the  ceiling  is  lower
             than 2300mm AFFL the ceiling beams should
             be omitted.
          2. The beams must always be 50mm deep.
          3.  Beams  must  have  end  cappings  when  not
             adjacent to wall.

          The  timber  ceiling  beams  will  be  supplied  by
          Paradigm  and  are  to  be  made  from  20mm
          Engineered  Oak  Flooring,  mitred  and  glued,
          finished  with  20%  lacquer.  The  beams  will  be
          mechanically  fixed  to  9mm  MDF  hanging
          pattresses, secured on site via proprietary unistrut
          system to  manufacturer’s details and  installed
          on-site by the contractor via M8 threaded bars.

          Beams  are to be provided in two standard
          lengths of 1900mm and 3800mm but can be cut
          on site, providing varying beam lengths to suit the
          project drawings. The 3800mm beams consist of
          two 1900mm beams joined together by 150 x 60
          x 20mm solid timber jointing pattresses.



















          2.5.3                      Timber Ceiling Beams                                   30 May 2018