4.3.6 Induction Loop                                  4.3.7 Oven and Fan Wiring
          Induction  Loops  to  assist  the  hard  of  hearing   The  main  site  electrician  will  be  required  to
          must be installed in all new stores and all re-fits   supply  simple  on/off  switches  and  wire  to
          from the beginning of 2012. This will normally be     isolator adjacent to each fan.
          fitted to the Disabled section of the counter and
          may be fitted by the site electrician as part of      The electrical supply to each oven socket must
          his installation. The unit fitted should comply with   be independent, so that in the event that one
          EN60118-4 (formerly BS6083) and BS7594:2011. A        circuit breaker trips, power is  not lost to both
          suitable unit is SigNET ML1/K.                        ovens at the same time.


                                                                On  activation  of  the  gas  interlock  /  fire  alarm
                                                                both  gas  and  electrical  supplies  to  the  ovens
                                                                must turn off.
















































          4.3.6                      Induction Loop                                         30 May 2018
          4.3.7                      Oven and Fan Wiring                                    3 September 2018