Page 75 - B8773-AEW-XX-XX-PP-A-0001_[P8]_Contractors Manual
P. 75

4.3.3 Removal of Existing Installations
          The Contractor shall strip out and dispose of any     •  Identify  every  out-going  way  with  a
          existing redundant electrical installations.   This       renewable  circuit  chart  in  a  transparent
          should  normally  include  everything,  back  to          plastic  envelope  permanently  fitted  inside
          the  meter.  Existing  equipment  should  only  be        the distribution board cover.
          considered for re-use where it is in good condition   •  Clearly  indicate  in  typed  script,  circuit
          and complies fully with the requirements of the           identification  number,  cable  size,  circuit
          project and the current IEE regulations.                  breaker rating and a description of the item
                                                                    and area supplied by the circuit.

          4.3.4 Mains Distribution                              •  Note that the Air Conditioning and Coldroom
                                                                    circuits MUST utilise Type 3 breakers to cope
          •  Liaise   with   the    electrical   distribution       with start loads.
             company,  as  necessary,  to  confirm  or          •  Carry  out  the  installation  of  an  earthing
             determine  that the  main supply head fuse             system  in  accordance  with  BS7671  and
             is rated at 100 amps, if single phase. Advise          BS7430.
             DPG if this is not the case.                       •  Provide  a  main  earth  bar  at  the  incoming
          •  Except  in  exceptional  circumstances,  DPG           service position, together with a clean earth
             will normally have arranged for any existing           bar for computer circuits.
             single phase incoming supply and/or meter          •  Ensure that all items of fixed metal equipment
             to  be  upgraded  to  a  3-phase  supply  and          are correctly earth bonded.
             meter.                                             •  Ensure that the phases are correctly
          •  Wherever a 3-phase meter is installed, then            balanced.
             the  shop  installation  MUST  be  arranged  to
             take balanced loads from all 3 phases.
          •  Supply  and  install  a  new  MCB  distribution    Wiring Installation
             board. This shall be suitably sized to meet the    •  Final circuit wiring shall be carried out using
             requirements of the installation and allowing          concealed  BASEC  certified  flat  cabling  to
             25%  spare  capacity  within  the  board  for          BS6004 or LSZH to BS7211.
             future expansion or alteration.                    •  Ensure  that  all  cables  are  fixed  at  least
          •  Normally,  install  the  board  adjacent  to           200mm from hot water pipes.
             the  incoming  main  and  metering,  unless
             otherwise agreed in specific circumstances.
          •  Install  the  board  so  that  any  covers/doors
             may be opened on their hinges and do not
             have to be lifted off to gain full access. In
             accordance with requirements for Electrical
             Installations,  IET  wiring  regulations,  18th
             edition, BS 7671:2018.





          4.3.3                      Removal of Existing Installations                      3 February 2016
          4.3.4                      Mains Distribution                                     3 September 2018
   70   71   72   73   74   75   76   77   78   79   80