4.3 Electrical and Small Power




          4.3.1 Electrical Meter Cupboard
          A  proper,  30  minute  fire  rated  cupboard  is
          required  around  all  electrical  switchgear  and
          metering installations.
          Not  only  must  distribution  boards,  meters  and
          other  such items be enclosed in a proper
          cupboard,  but the  clearances in front  are
          specified  and  the  need  for  enough  room  to
          work to replace any faulty items is also specified.


          This  means  that  the  off-the-shelf  access  doors
          that some contractors like to use are barely big
          enough and if used they MUST be positioned to
          give the regulation access.


          The ideal is a 30 minute fire rated hinged door
          although  it  doesn’t  necessarily  need  to  be  a
          full size person door. Please note also, that if a
          cupboard needs to be built, then it must be sized
          to not only contain the electrical equipment but
          must  still  allow  clear  passage  for  anyone  who
          needs to get past in the corridor.


          The following sketch illustrates, in general terms,
          what is required.






          Door and cupboard
          enclosure to be fire
          rated to a min. of 30
          minutes, lockable, with
          appropriate signage.















          4.3.1                      Electrical Meter Cupboard                              30 May 2018