Page 92 - B8773-AEW-XX-XX-PP-A-0001_[P8]_Contractors Manual
P. 92

4.6.2 Cold Water                                      4.6.3 Sink Waste
       •  Cold water installation shall commence from        Problems  have arisen with  lack of  capacity
          the incoming mains stop-cock in the position       within the  drains from  the triple bowl sink. The
          indicated on drawing.                              main contractor  shall  size the pipework such
       •  A double check valve to Water Regulations          that there is free flow of waste water when all
          specification  shall  always  be  installed        three sink bowls are emptied at once, and so
          adjacent to the main incoming stop tap.            that if 2 bowls are emptied at once, there is no
       •  Cold  water  pipework  shall  be  run  in  light   back flow into the third bowl.
          gauge  copper  tube  and  installed  as  the
          domestic hot water pipework.
       •  All pipework shall be insulated as the domestic
          hot water pipework with the addition of an         4.6.4 Thermostatic Blending Valve
          integral vapour barrier (Dunlop Armourflex/        Where  a  thermostatic  blending  valve  is  fitted,
          Foamflex or equivalent and approved).
       •  Updated water-log-book to be provided by           i.e  for  the  knee  operated  whb,  etc,  this  MUST
                                                             be  installed  not  more  than  2  metres  from  the
          main contractor in O+M manual.
       •  Stop  tap  location  to  be  recorded  in  O+M     appliance which it serves, to comply with water
                                                             industry regulations.
          manual.
       •  Where a hood type pass through dishwasher
          is to be installed the water supply requirement
          is a 22mm connection via 2m flexible hose
          (female termination). Water supply 15 C to
                                                   o
          60 C (2  to 8 clark max) at 0.4 to 10.0 bar
                  o
             o
                        o
          max.
       •  For dishwashers (and washing machines) the
          contractor  must allow for  foul water drain
          connection as appropriate.
       •  L8  risk  assessment  and  management  plan
          to be issued by the Principal Contractor on
          project handover.

















       4.6.2                       Cold Water                                            3 September 2018
       4.6.3                       Sink Waste                                            30 May 2018
       4.6.4                       Thermostatic Blending Valve                           30 May 2018
   87   88   89   90   91   92   93   94   95   96   97