Page 97 - B8773-AEW-XX-XX-PP-A-0001_[P8]_Contractors Manual
P. 97

4.7.3 Fresh Air Supply
          The supply air installation shall take the form of    At the conclusion of the installation, the HVAC
          a  suitable  inlet  louvre  with  bird/rodent  guard   contractor  shall fully commission  the  entire
          and sized on a min. free area of 50% and max.         system  including  both  duct  systems  and  the
          velocity of 2.5m per second. The system shall be      gas safety interlock, and shall check by on-site
          complete with a fresh-air filter to EU4 standard,     measurement  that  the  airflows  are  within  his
          an  axial  flow  fan,  and  a  range  of  ductwork    appropriate designed parameters.
          terminating  in  ceiling  mounted  diffusers,  with
          integral  dampers  accessible  through  the           The  ventilation  of  internal  toilets  shall be
          diffuser face, and finished to match the ceiling      controlled by the light switch, being interlinked
          colour. The fresh-air systems shall be designed       with the extract fan timer. Internal offices shall
          to replace approximately 80% of the extract air       have a further fresh air supply,  either with
          volume.                                               independent control or as part of the supply air
                                                                system.
          Internal ceiling grilles in the Bake & Serve and
          Customer area’s MUST be sprayed to RAL 7037           For specific ventilation requirements please refer
          (matt  finish)  to  match  the  grey  ceiling  colour.   to the oven manufacturers recommendations.
          Grilles in other areas must match ceiling colour.
                                                                O&M manuals must be provided by the Principal
          As  part  of  the  initial  installation,  the  HVAC   Contractor on project handover.
          contractor  shall  include  a  nominal  12  months
          supply of replacement fresh air filters.


          The design of the system must take into account
          the requirement for approved specialist
          cleaning  contractors  to  be  able  to  change
          the fresh air filters on a regular basis. The fresh
          air  filter  must  be  located  in  an  accessible
          position,  and  orientated  so  that  the  cleaning
          contractors are able to access the filters easily,
          including positioning so that the access panel is
          not obstructed by walls, ceilings, pipework, etc.
          and that there is sufficient space in front of it for
          the replacement panel. Liaison with the main
          contractor to achieve this will be required.


          Both exhaust ductwork outlet and fresh-air inlet
          points shall be located to minimise short circuiting
          so that exhaust air cannot be drawn back into
          the building through openable windows etc.



          4.7.3                      Fresh Air Supply                                       3 September 2018