Step 5

                   Sealing & Assembling Containment Walls

                          Make sure floor is clear of any debris.  Sealing should be done as
                          containment walls are assembled.  Apply a 3/8” bead of acid-resistant
                          sealant to the bottom surface of each containment barrier wall as they are
                          put into place. To insure liquid-tight containment around base of
                          components, apply a 3/8” bead of acid-resistant sealant around the inside
                          of the containment as well as around all feet of the battery rack(s).

                     Applying Sealant to barrier walls is required with all applications












                                                          Figure 5


                          Place the floor anchor bolts in the drop-in floor anchor assemblies and
                          hand-tighten floor anchor bolts.  As you install each barrier wall to the
                          floor, apply 3/8” bead of sealant at the vertical joints of the components.
                          Bolt and tighten each containment wall as it is added to the assembly
                          (torque to 110 inch/lbs).  After the components have been attached,
                          secure the assembled barrier wall to the floor by tightening the floor
                          anchor assembly bolts using a 7/16” socket (torque to 110 inch/ lbs).
                          Apply a 3/8” bead of sealant along the inside of the containment walls.  A
                          small amount of water may be used to help smooth the sealant and
                          enhance the bead of the seal.


                                               Sealant Bead
                                                         3/8” Bead
                                             Wipe Off Excess



                                                          Figure 6