Page 301 - Womens Pavilion
P. 301

Oil-Less Claw Medical Vacuum


           Appendix A:  TotalAlert Embedded Control System



           A.2.4   5.7” Main Screen                            •  If the unit is unavailable because the unit is
                                                                   an expandable unit, that color bar shows dark
                                                                   grey and the adjoining symbol shows “E”.

                                                               •  If the unit is unavailable because the unit
                                                                   cannot be reached via ethernet, that color
                                                                   bar shows dark grey and the adjoining symbol
                                                                   shows “?”.

                                                               A.2.5   5.7” Trend Screen









           Figure A.6 Main Screen (VSD shown)

           The main (default) screen (Figure A.6) shows the
           pertinent system measurements as well as unit
           sequence information.

           The pertinent system measurements include:
           Vacuum Level and VSD Level (for VSD systems).
           Pressing pertinent system data buttons shows
           Trend information for that value.                   Figure A.7 Trend Screen

           Unit Sequence information shows all system units.    The trend screen (Figure A.7) shows the measured
                                                               value over a specifi c time period:
           •  If the unit is running, that color bar shows
              green and the adjoining symbol shows “*” for     •  The default time period when opening the
              across the line (full speed) or “~” for variable     window is the last 60 minutes.  For a given
              speed drive.                                         period, the maximum amount of data stored
                                                                   will only be for the most recent time period
           •  If a unit is available and not running, that color   and the older data will be removed from view
              bar shows blue and the adjoining symbol              and memory.
              shows “+” if that unit is next to start.

           •  If a unit is stopped, that color bar shows red   •  Another time period is selected by pressing the
              and the adjoining symbol shows “!” if stopped        buttons at the bottom of the window.  These
              for a shutdown.                                      periods are 60 minutes (240 data points – 0.25
                                                                   min resolution), 4 hours (240 data points – 1
           •  If the unit is unavailable and not running, that     min resolution), 24 hours (240 data points – 6
              color bar shows dark grey and the adjoining          min resolution) and 6 days (240 data points –
              symbol shows “X”.                                    0.6 hour resolution).

           •  If a unit is unavailable because it is in Manual
              mode and it is running, that color bar shows
              green and the adjoining symbol shows “X”.


           4107 9000 95.04                                  A-4