TotalAlert Infinity™ NFPA Medical Gas Notification System
Set Clock
1. Click Clock Setup to access the Clock
Setup page (Figure 195).
2. Set the current date by inputting the year,
month, and day.
3. Set the current time by inputting the cur-
rent hour and minutes.
4. Click the SET tab to complete. Whet the
SET tab is pressed, the date and time are
set on the system and seconds are set to
zero. Figure 196: Setup Device Page
To provide input for the TotalAlert 1 network:
1. Click Device Setup to access the Setup
Device page (Figure 197).
2. Select Compatible Location of the
TotalAlert Infinity™ alarm by using pull
down menu.
3. Enter the Zone for the TotalAlert Infinity™.
4. Enter Floor location.
5. Enter Direction.
6. Enter Compatibility Mode.
Figure 195: Clock Setup 7. Click Submit.
Device Setup
Network Setup
This setup page is used to configure alarm
name, location, facility name, and contact CAUTION:
information. The page also provides input for The Information Systems personnel should
TotalAlert1 compatibility if the TotalAlert In- be notified before changing any of the
finity™ needs to be enrolled on the TotalAlert network settings. Changing the settings may
1 network.
prevent the equipment from working prop-
1. Click Device Setup to access the Setup erly.
Device page (Figure 196).
2. Enter the Alarm name. 1. Click Network Setup to access Network
setup page (Figure 197).
3. Enter the location.
4. Enter the facility name. 2. Select the DHCP Mode (Enabled/Dis-
abled).
5. Enter the Contact Information.
6. Click Submit. If Disabled:
1. Enter the IP Address.
2. Enter the Subnet Mask.
3. Enter the Default Gateway
4-49 4107 9016 58.02