TotalAlert Infinity™ NFPA Medical Gas Notification System
Figure 198: Network Setup Page Figure 199: Website Setup Page
The TotalAlert Infinity™ Alarm allows for Electronic Notification
Automatic Discovery Broadcast on other This setup page is used to configure elec-
TotalAlert devices. This setting allows for tronic notification (e-mail, pager, phone text
other TotalAlert devices to find the TotalAlert message). The alarm panel acts as an SMTP
Infinity™ alarm on the network and automati- client. An SMTP server is required for elec-
cally enroll the device. tronic notification to function. The TotalA-
To enable Automatic Discovery: lert Infinity™ website has the ability to setup
1. Select Enabled on the Network Setup email notification for all messages, all gases,
page to set Automatic Discovery Broad- or specifically up to 3 gases.
casts. By setting up the Electronic Notification,
2. Click Submit. key personnel can receive notifications of all
Website Setup alarm events.
The TotalAlert Infinity™ Website has several An SMTP e-mail server must be configured in
options for the Auto-refresh feature on the order for Electronic Notifications to function.
web page. This determines the frequency by Click “Set Up Email Server” to configure the
which Status pages are automatically up- server (Figure 200).
dated. 1. Click Electronic Notification to access the
1. Click Website Setup to access Auto-refresh Electronic Notification setup page (Figure
time menu (Figure 199). 200).
2. Choose increments from 5 seconds to 2. Enter an e-mail address. Up to twelve e-
4 minutes to refresh. Select Disable to mail addresses can be set up.
remove Auto-refresh and manually update 3. Choose All Messages, All Gases, or Specific
data when needed. Gases (up to 3) from pull down menu.
3. Click Submit. 4. Click Submit.