Page 518 - Womens Pavilion
P. 518
TotalAlert Infinity™ NFPA Medical Gas Notification System
Data Line Layer Options: ISO 8802-3 (“Ether-
net”) LAN Character Set Support: ISO 10646
(UTF-8) Encoding.
1. Click BACnet Setup to access BACnet
Setup page (Figure 201).
2. Enter BACnet Device ID#.
3. Enter BACnet Device Name.
4. Choose to Enable or Disable BACnet Com-
munication.
5. Click Submit
Figure 200: Electronic Notification Setup Page
BACnet Setup
The BeaconMedæs TotalAlert Infinity™ NFPA
control systems utilize the TCP/ IP family of
protocols for communication and each alarm
has a unique IP address.
Each BACnet enabled TotalAlert Infinity™
alarm conforms to the BACnet protocol.
• Protocol Implementation Conformance
Each BACnet enabled TotalAlert Infinity™ Figure 201: BACnet Setup Page
alarm has available a Protocol Implementa-
tion Conformance Statement (PICS). The PICS Clear Event Log
is a written document created by Beacon- 1. Click Clear Event Log to access the Clear
Medæs that identifies the particular options Event Log page (Figure 202).
specified by BACnet that are implemented in 2. Click Clear Event Log.
the TotalAlert Infinity™ alarm.
• BACnet Conformance
BACnet Vendor ID: 543
Alarm Profile: BACnet Smart Sensor (B-SS)
BIBB (BACnet Interoperability Building
Blocks) Supported:
• Read Property - B (DS-RP-B)
• Dynamic Device Binding - B (DM-DDB-B)
• Dynamic Object Binding - B (DM-DOB-B)
Object Type Support: Analog value, Binary Figure 202: Clear Event Log
value, Device.
CAUTION:
Be sure to save the event log prior to clear-
ing it. It is impossible to recover the event
log after it is cleared.
4-51 4107 9016 58.02