TotalAlert Infinity™ NFPA Medical Gas Notification System



           1.  Locate the Ground cable attached to the
              power supply and connect the ring ter-
              minal end to the rough-in box for chassis
              ground.  Use the self-drilling screw pro-
              vided.
           2.  Remove the 4 corner screws from the
              power supply cover and remove the cover.
           3.  Connect the supply power Line and Neu-
              tral wires to the terminal block.
           4.  Connect the supply power Ground wire                       Figure 215: DIP Switch Setting
              directly to the rough-in box.                    5.  Connect all input signal / output signal /
           5.  Replace the power supply cover and                  gas sensor wiring to their respective mod-
              screws.                                              ules.  Refer to the wiring diagram on the
           5.2.3 Install New Components                            Quick Setup Guide for instructions.

           1.  Determine the best placement of the re-         5.2.4 Install Trim Plate
              maining I/O modules inside of the rough-         Mega Master / Area 4 Gas
              in box.
                                                                  a.  Install trim plate assembly to rough-in
            NOTE: I/O Modules and Power Supply will                  box using the provided screws and/or
            need to be daisy chain connected via the                 drywall anchors.  Slots in the trim plate
            grey cables supplied with each I/O module.               will align with existing holes in the
                                                                     rough-in box flanges (Figure 216).
           2.  Mount the I/O Modules inside the rough-
              in box using the supplied hardware.               NOTE: Trim ring portion can be removed
           3.  Connect the grey cable(s) provided; from         from the trim plate if the surrounding wall
              the power supply to the white sockets on          area is in good condition. Mounting of the
              the I/O modules in a daisy chain manner           trim ring only to the rough-in box will result
              (Figure 214).                                     in a cleaner retrofit installation.
                                                               TA2/Mega2 Area 8 Gas

                                                                  a.  Remove the trim ring from the standard
                                                                     trim plate and install the wide 27” wide
                                                                     x 16” tall trim plate from retrofit option
                                                                     kit (4107220615). Screws are provided
                                                                     in the option kit for attaching the trim
                                                                     ring to the trim plate (Figure 216).
                                                                  b.  Install trim plate assembly to rough-in
                                                                     box using the provided screws and/or
                Figure 214: Daisy Chain of Power Supply              drywall anchors. Slots in the trim plate
           4.  The last module in the chain needs to                 will align with existing holes in the
              have the #1 DIP switch set to “ON” (Fig-               rough-in box flanges.
              ure 215).  Refer to the module ID label.