TotalAlert Infinity™ NFPA Medical Gas Notification System



           4.9 Wireless Ethernet Set-Up                        •  Touch the WIRELESS ETHERNET tab.
                                                               •  To turn the WIFI on, touch the WIFI STA-
           The TotalAlert Infinity™ Medical Gas Notifi-            TUS/ ON tab.
           cation System allows for Wifi 802.11 b/g/n          •  To change the WIFI password—STRONGLY
           interface which provides access to the alarm            RECOMMENDED—touch the WIFI PWD-
           panel web page with any web enabled de-                 tab. Using the keyboard, enter a new
           vice. Operating information and Event History           password.
           can be viewed and downloaded to the web             •  Touch the Save button to close and return
           enabled device.                                         to the WIFI SETTINGS screen.
           Wireless Ethernet Settings Tab                      •  To add the WIFI settings to the INFORMA-
                                                                   TION screen, touch the ALLOW WIFI CON-
           On the Miscellaneous screen, select the                 TROL / ON tab. The INFORMATION screen
           WIRELESS ETHERNET tab.                                  will now display a WIFI tab (Figure 205).


                                                                NOTE:
                                                                This will allow WIFI to be turned on/off
                                                                without a password.












                  Figure 203: Wireless Ethernet Tab

           The WIRELESS ETHERNET screen allows for
           customization of the WIFI settings. All of the
           tabs on this screen are set to default status.
                                                                      Figure 205: Wireless Ethernet Screen
                                                               •  Save settings.
                                                               •  Turn on the Web enabled device.
                                                               •  Find the wireless Ethernet network on the
                                                                   device with the SSID name.
                                                               •  Type in the password (default is 121212)
                                                                   on the web enabled device.
                                                               •  Open the browser and enter the IP ad-
                                                                   dress (default is 192.168.50.1) to go to
                                                                   the TotalAlert Infinity™ home page. This
                                                                   page displays active alarms, gas pressure
                 Figure 204: Wireless Ethernet Screen              signals, Network devices, device informa-
                                                                   tion, and the event log.