Page 55 - SIM Guide to annual assessment_v2.0_Dec 2021
P. 55
Grating and Checker Plates
LOAD BEARING LIMITATIONS
INCLUDES:
▪ Information plates or panels regarding the bearing limits of the platform /
walkway must be visually available at site.
▪ Platform duty is respected.
▪ Deflection caused by a loaded platform must be within the deflection limits
th
(1/200 of the span)
GOOD PRACTICE:
▪ Authorized storage areas in a platform must be physically demarcated on site with its
limits clearly indicated.
REMARKS: (according to ISO 14122)
The minimum operating loads calculated for the landing, walkways and working
platforms are usually:
o 2 kN/m2 under distributed load for the structure
o 1,5 kN concentrated load applied in the most unfavorable position over a concentrated
load area of 200 mm x 200 mm for the flooring.
th
o When loaded with the design load, the deflection of the flooring shall not exceed 1/200
of the span and the difference between the loaded and the neighboring unloaded flooring
shall not exceed 4 mm in height.
NOTES:
55