Page 89 - Condition Monitor User Manual
P. 89

Configuring a Monitor



































                                     Figure 7-32 Original GuardII OC Trigger Configuration
                          Once the data is entered, review it and make sure that it is correct.  Then press the
                       ‘Confirm’ button.

              7.6.3.  GuardII+ OC Trigger Configuration

                          OC Trigger configuration for the GuardII+ is used to configure the Operating Conditions
                       that are used in the PD Trigger system in the monitor.  Press the ‘OC Trigger’ button on the
                       ribbon.
                          Enter  the  load  and  temperature  values  that  corresponds  to  the  different  Operating
                       Points:
                          •  Minimum ‘Full’ load

                          •  Maximum ‘Reduced’ load
                          •  Minimum ‘Hot’ temperature

                          •  Maximum ‘Cold’ temperature
                          Optionally, enable User Defined Trigger and set the time interval and minimum asset
                       QM that is used to evaluate the User Defined Trigger.
                                       Note:
                                       Refer to the GuardII+ PD user Manual for details on the operation of
                                       the Triggers.









                                                            83