Page 91 - Condition Monitor User Manual
P. 91

Configuring a Monitor



              7.6.4.  GuardII PD Trigger Configuration

                          PD Trigger configuration sets the QM thresholds for the PD level Triggers.  Press the
                       ‘PD Trigger’ button on the ribbon.

                          Enter the QM thresholds for the Moderate, High and Very-High PD level Triggers.  A
                       separate  threshold  can  be  entered  for  Asset  and  Total  System  Activity  (for  BUS  PD
                       systems), for C1 and C2 (for PDA PD systems) and for Endwinding and Total Slot Activity
                       (for SSC PD systems).

                          Use the ‘Load Defaults’ button to set the thresholds based on the asset ratings.
                                       Note:
                                       Default PD Alert thresholds are based on a statistical analysis of PD
                                       activity in similar assets.  In some cases, the combination of asset
                                       parameters  may  not  have  enough  statistical  data  to  recommend
                                       default PD alert thresholds.

                          Once the data is entered, review it and make sure that it is correct.  Then press the
                       ‘Confirm’ button.
































                                         Figure 7-34 GuardII PD Trigger Configuration















                                                            85