Page 87 - Condition Monitor User Manual
P. 87

Configuring a Monitor




                                       Note:
                                       If using the Detect Sensitivity function it is recommended to visually
                                       check  the  data  collected  using  the  ‘View  Measurement’  button  to
                                       make sure that the detected sensitivity is correct.

                          The ‘Run Measurement’ button will run a measurement using the selected Sensitivity.
                          The ‘View Measurement’ button will show you the last measurement that was run.  When
                       evaluating the measurement to see if the sensitivity is appropriate, check the following:
                          •  The Measurement Status should be reported as ‘OK’.

                          •  The Measurement Quality should be reported as ‘OK’.  If the Quality is reported as
                              ‘Alert’,  this  means  that  the  QM  results  exceed  the  currently  configured  Alert
                              thresholds,
                          •  The largest QM should be no more than 50% of the selected sensitivities’ maximum
                              voltage.  For example, if the sensitivity is set for 20-340 mV, then all QM values
                              should be ideally less than 170 mV.  This allows for PD to increase over time and
                              build a good trend before needing to set a new sensitivity.






















                                                Figure 7-31 View Measurement

                          On the View Measurement page, you can also save the measurement to the database
                       if desired.

              7.6.2.  Original GuardII OC Trigger Configuration

                          OC  Trigger  configuration  for  the  original  GuardII  is  used  to  configure  the  Operating
                       Conditions that are used in the PD Trigger system in the monitor.  Press the ‘OC Trigger’
                       button on the ribbon.
                          Enter  the  load  and  temperature  values  that  corresponds  to  the  different  Operating
                       Points:
                          •  Minimum ‘Full’ load

                          •  Maximum ‘Reduced’ load



                                                            81