Configuring a Monitor
Note:
Partial discharge activity typically changes slowly over months or
years. While it is possible to use the User Defined Trigger to collect
daily data (or even more), this will only unnecessarily inflate the
database for no benefit.
The recommended use of the User Defined Trigger is to capture a
brief period of rapid data collection after maintenance activity that
could affect the PD levels or to capture transient spikes in PD activity.
Figure 7-33 GuardII+ OC Trigger Configuration
Pressing the ‘Load Defaults’ button will calculate all of these values based on the asset
ratings:
• ‘Full Load (min)’ is set to 80% of the rated load.
• ‘Reduced Load (max)’ is set to 50% of the rated load.
• ‘Hot (min)’ is set to 80% of the rated temperature.
• ‘Cold (max)’ is set to 70% of the rated temperature.
Once the data is entered, review it and make sure that it is correct. Then press the
‘Confirm’ button.