Page 32 - GuardII+ Series 4208 Platform User Manual
P. 32
Installation
Shorted External and AC
Isolated Ground
Power Grounds
Figure 5-8 Ground Isolation
5.9. Power Connections
GuardII+ requires a power source quality like that needed for control and protection
devices and should include a circuit breaker. The nominal input voltage is either 115 Vac or
230 Vac and an internal switch is used for selecting the fusing for the ac power.
WARNING:
The main ac circuit breaker providing power to the GuardII+ should be
turned off when accessing the GuardII+ AC Termination Board.
2
Supply wiring should be 0.82 mm (#18 AWG) stranded (16x30) or larger
tinned copper conductor with PVC insulation. The cable should be rated
105 °C, 600 V or equivalent according to local country electrical codes.
The ac power connections are made at the AC Termination Board on the electronics
assembly.
Figure 5-9 AC Power Input Connection
26