Page 32 - GuardII+ Series 4208 Platform User Manual
P. 32

Installation











                                                                   Shorted External and AC
                                       Isolated Ground
                                                                       Power Grounds
                                                 Figure 5-8 Ground Isolation

              5.9.  Power Connections

                        GuardII+  requires  a  power  source  quality  like  that  needed  for  control  and  protection
                     devices and should include a circuit breaker.  The nominal input voltage is either 115 Vac or
                     230 Vac and an internal switch is used for selecting the fusing for the ac power.

                                     WARNING:
                                     The main ac circuit breaker providing power to the GuardII+ should be
                                     turned off when accessing the GuardII+ AC Termination Board.
                                                                     2
                                     Supply wiring should be 0.82 mm  (#18 AWG) stranded (16x30) or larger
                                    tinned copper conductor with PVC insulation.  The cable should be rated
                                     105 °C, 600 V or equivalent according to local country electrical codes.

                        The  ac  power  connections  are  made  at  the  AC  Termination  Board  on  the  electronics
                     assembly.



















                                            Figure 5-9 AC Power Input Connection


















                                                            26