Incident

































                                                   Damaged Cable




             Root Cause

            Damage of cable while excavation & non adherence to work permit system.



             Recommendations

           1. Manual excavation shall be done at designated locations on the route before starting mechanized
              excavation.
            2.  Excavation permit is must from concerned departments as per procedure within battery limit and
              township.

            3.  Lying of cable must be as per IE rule & IOCL standard.

            4.  For Outside Battery limit, P&U is to issue a drawing showing cable route so that excavation can be done
              along the said route.

            5.  Any abnormality while working like cable damage in this case, that is to be reported immediately to site
              in charge / owner in charge.





             Case 4                               Date: 06.08.2019                       Time: 17:45 hrs.



             Incident

            During erection of a 10“ pipe in main pipe rack of Prime-G using hydra & chain pulley block, an armored
            cable got crumpled in between pipe and concrete beam of pipe rack causing spark.