Root Cause
Poor area preparation at (FOR) hot job.
Recommendations
1. Ensure all bolts/studs of HC line blind flanges are tightened completely.
2. Hot job site shall be barricaded properly while welding, grinding activities.
Case 10 Date: 26.09.2019 Time: 20:24 hrs.
Incident
Sparking occurred in 300 mm, 440Volt, 3.5 core underground power cable laid from CISF Sub-station to
officer's married hostel. Insulation of underground power cable has got damaged during excavation job by JCB
being carried out for laying underground drinking water line, As the load increased on the cable and exposed
to moist air, sparking occurred on the damaged portion of cable. Cable marker is also placed at the site but got
ignored due to poor supervision.
Electrical Cable Damaged cable
Route marker
Root Cause
Contactor supervisor ignored the cable route marker.
Recommendations
1. Manual excavation shall be done at designated locations (where cable markers are placed to know the
exact location of cable) on the route before starting mechanized excavation.
2. For Outside Battery limit, Elect Maint to issue a drawing showing cable route so that mechanized
excavation is only done along the said route after completion of manual excavation.
3. Any abnormality like cable damage while excavation, should be reported immediately to site in
charge / Engineer in charge.