Survey Report Contents Overview Services Internal External Total Est. Costs 11
WC
WC Lighting not IP rated No sealant
Gap in flooring
Details / Defects / Issues: Yes. Items of concern have been listed below.
Extraction
No form of mechanical extraction is fitted within the room. You are advised to install a mechanical means of
ventilation, in line with Approved Documents F and L of The Building Regulations 2010. This will need to be in the
form of an extractor fan with a 15 minute overrun timer facility. A 3-pole isolation switch will also need to be
installed. You are advised to seek further advice from an electrician and undertake remedial work as recommended.
Estimated Costs £400-500.00
Electrical Installation
The lighting is not suitably IP rated and presents a safety issue. As part of any electrical repairs and upgrades the
lights will need to be replaced with IP rated fittings.
Estimated Costs £120-150.00