Page 83 - GuardII+ Series 4208 Platform PD User Manual
P. 83

Troubleshooting






















                                     Figure 7-10 Acceptable PD Tester Variation Examples
                        Indications of hardware failure include:

                        •  A peak split across more than 2 amplitude windows.
                        •  A peak that appears more than 1 amplitude away from its ideal position.

                        •  A complete peak occurring at more than one amplitude window.
                        •  A peak is missing.




















                                    Figure 7-11 Unacceptable PD Tester Variation Examples

              7.3.  AC Synchronization

                        Use this procedure for troubleshooting ac synchronization problems.  This is characterized
                     by the downloaded measurements reporting a ‘No Sync’ status in the IAM software suite.

                                     NOTE:
                                     When there is no ac synchronization signal, only 2 PD Triggers can occur:

                                       •  Time-Based Trigger described in Section 4.6.3

                                       •  User-Defined Trigger described in Section 4.6.10 (only if enabled,
                                          and only if a minimum Qm threshold is not selected)





                                                              75
                                                                                          www.irispower.com