Page 83 - GuardII+ Series 4208 Platform PD User Manual
P. 83
Troubleshooting
Figure 7-10 Acceptable PD Tester Variation Examples
Indications of hardware failure include:
• A peak split across more than 2 amplitude windows.
• A peak that appears more than 1 amplitude away from its ideal position.
• A complete peak occurring at more than one amplitude window.
• A peak is missing.
Figure 7-11 Unacceptable PD Tester Variation Examples
7.3. AC Synchronization
Use this procedure for troubleshooting ac synchronization problems. This is characterized
by the downloaded measurements reporting a ‘No Sync’ status in the IAM software suite.
NOTE:
When there is no ac synchronization signal, only 2 PD Triggers can occur:
• Time-Based Trigger described in Section 4.6.3
• User-Defined Trigger described in Section 4.6.10 (only if enabled,
and only if a minimum Qm threshold is not selected)