Page 85 - GuardII+ Series 4208 Platform PD User Manual
P. 85

Troubleshooting



































                                      Figure 7-13 Check Synchronization Source Setting
                        •  If the Synchronization Source is not correct, enter the correct value and upload the
                            changes.  Once this is done, check to see if the synchronization problem still exists.
                            This can be done quickly with the single-shot measurement.
                        Note  that  further  troubleshooting  synchronization  problems  requires  some  additional
                     equipment.  Basic troubleshooting requires a voltmeter that can measure frequency as well
                     as  voltage  (most  digital  voltmeters  can).    More  advanced  troubleshooting  requires  an
                     oscilloscope.
                        •  Go to Section 7.3.2 for sensor-based synchronization.

                        •  Go  to  Section  7.3.3  for  external-based  synchronization  (connected  to  the  AC
                            Termination board).

                        •  Go to Section 7.3.4 for low-voltage external-based synchronization (connected to the
                            Carrier board).

                        •  Go to Section 7.3.5 for ac power-based synchronization.

              7.3.2.  Sensor-Based Synchronization
                        Use this procedure if the GuardII+ is using the PD sensor as a synchronization source.
                     This is the most common configuration for BUS and PDA systems but cannot be used for SSC
                     sensors.