4.5.3 Fire Alarm
          Design,  supply  and  install  a  fire  alarm  system
          in  accordance  with  all  current  Building  Regs
          standards and as the project drawings.

          The  design  should  note  the  requirements  of
          BS5839 Section 1- part 6, Section 4 -part 36, 39 &
          41, Section 6 - part 44 & 45 in particular.

          The system should incorporate a battery backed
          control  panel, manual call  points, automatic
          detectors and sounders, as required by Building
          Inspector  and  Fire  Officers  for  each  specific
          project.


          The  control  panel shall incorporate  a facility
          to  link  with  other  fire  alarm  systems  within  the
          complex, where required, so that fire signals can
          be received from others as well as transmitting a
          fire signal to others.

          The panel MUST display the emergency number
          to call in the event of faults to the system. The
          panel must display the reset code.
          All  wiring  to  the  fire  alarm  system  shall  be
          carried  out  using  concealed  BASEC  certified
          red sheathed mineral insulated or fire resistant/
          performance  cabling  complying  with  BS6360
          Class 2 and meeting the requirements of BS6387
          Category CWZ.


          Allow to demonstrate the system  to the
          franchisee at handover.


          All  installation,  commissioning  and  O&M
          manuals must be provided by the  Principal
          Contractor on project handover.