Page 625 - Med Plaza and Cancer Center
P. 625

PROPRIETARY AND CONFIDENTIAL DRAFT 28/Feb/03

                   Detailed Component Descriptions
                   Chapter 1: Introduction

                                 Table 1-3.  Browsing Options Available for the Master Alarm by Using the
                                                                 Web Pages

                             Browsing Option                           Description
                           Alarms                  Lists all of the alarm inputs that communicate with
                                                   this Master Alarm.
                           Event log               Log of events and alarms for all inputs that this Master
                                                   Alarm is monitoring.
                           Network statistics      Communication statistics used by Information
                                                   Systems personnel.
                           Hardware input states   Lists the state (open or closed) of the inputs.




                                 Building Automation System (N2) Mapping

                                 The MedPlus TotalAlert™ Alarm Network has the option of connecting to a
                                 facility’s building automation system (BAS). N2 mapping is an address that
                                 the alarm uses as an output to the BAS. An RS-485 connection physically
                                 interfaces the alarm with the facility’s BAS. If this option is used, both the
                                 alarm and the facility’s BAS receive alarms and alarm silences.

                                 The Master Alarm’s source inputs are the same number as the building
                                 automation’s inputs. For example; a “backup vacuum pump on” switch for
                                 vacuum system 3 is physically wired to position 5 on the Master Alarm
                                 Breakout P.C. Board, that means that the address on the N2 BAS is BYT5.


                                 NOTE:
                                 BYT is an 8-bit type of data that is used by N2 building automation systems.

                                 The status of the alarms used by the building automation system are as follows:

                                   • 0 = no alarm

                                   • 1 = alarm
                                   • 2 = alarm silenced

                                 If the MedPlus TotalAlert™ Area Alarm is set up to communicate on the
                                 Ethernet Network, the number of Area Alarm Modules on the network can be
                                 sent to the N2 building automation system. The Area Alarm Module
                                 information is sent as ADI5 data to the BAS.


                                 If there are three oxygen Area Alarm Modules and three vacuum Area Alarm
                                 Modules connected to the alarm network, the ADI5 data would equal six. If
                                 there are no Area Alarm Modules connected to the alarm network, the ADI5
                                 data would equal zero.




                   Page 1 - 28           MedPlus TotalAlert™ Alarm Network Operation and Maintenance Manual (man291ra)