Page 453 - Womens Pavilion
P. 453

TotalAlert Infinity™ NFPA Medical Gas Notification System



           2.2 Gas Sensor Installation                         2.2.2 Remotely Installed Sensors in
                                                               Pipeline
           2.2.1 Locally Installed Sensors
           1.  Locate copper adapter tube(s) packaged          1.  Sensors can be installed onto the hospital
              inside the alarm rough-in box.                       pipeline.
           2.  Install tube(s) into the top of the rough-      2.  Braze copper adapter tube(s) to
              in box through the holes provided.                   appropriate pressure/vacuum piping
              Notice the Gas ID labels and position                system connections (Figure 20).
              appropriately for connection to the              3.  Braze connections per procedures
              hospital piping. Apply Gas ID label                  required by NFPA 99 or CAN/
              provided with tube adapter to the                    CSA-Z7396.1-12
              inside of the rough-in box to identify           4.  Use appropriate measures to prevent
              the ports after walls are closed in.                 overheating.

           3.  Braze copper adapter tube(s) to                 5.  Install the Gas Specific DISS check valve
              appropriate pressure/vacuum piping                   into the appropriate tube adapter.
              system drops (Figure 19). Braze                  6.  Perform standing pressure test and cross
              connections per procedures required                  connection tests as required by NFPA and
              by NFPA 99 or CAN/CSA-Z7396.1-12.                    CSA.
              Use appropriate measures to prevent
              overheating.                                            Connection should    REMOTE SENSOR
           4.  Install the Gas Specific DISS check valve              be made on top of
                                                                      pipe
              into the appropriate tube adapter.
           5.  Perform standing pressure test and cross
              connection tests as required by NFPA and
              CSA.
                                                                    Figure 20: Remote Pipeline Installation
               Connection should            LOCAL SENSOR
               be made on top of                               2.2.3 Remotely Installed Sensors in
               pipe
                                                               Zone Valve Box

                                                               1.  Remote sensors can be installed in a
                                                                   compatible BeaconMedæs Zone Valve
                                                                   Box. (NOTE: copper adapter tube not
                                                                   needed for Zone Valve box installation
                                                                   (Figure 21).

                                                               2.   For Zone Valve Box mounting, an
                                                                   additional Installation Kit is required, part
                                                                   number 4107 4016 25 for each sensor.






                Figure 19: Sensor Pipeline Connection




           4107 9016 58.02                                  2-2
   448   449   450   451   452   453   454   455   456   457   458