TotalAlert Infinity™ NFPA Medical Gas Notification System




                CAUTION:                                       2.3.6 B1X Signal Board

                                                               A Master or Combination alarm panel can
           Do not connect TotalAlert Infinity™ master/         contain multiple signal input boards; up to a
           combination alarm to switch/relay contacts          maximum of 3 boards or 60 signal inputs.
           connected to any alarm panels other than
           those listed below:                                 Input signals on B10, B11, B12 boards are
                                                               labeled X01 thru X20.
           •  TotalAlert Infinity™
           •  TotalAlert2                                      Identify each twisted pair of field installed
           •  MEGA3                                            signal input signal wires inside the alarm
           •  MEGA2                                            rough-in box.
           •  MEGA                                             Route each pair of signal input signal wires as
                                                               shown in Figure 26 to appropriate terminals
                                                               on input board(s).
                                                               Connect each pair of signal wires to terminal
                                                               blocks noting the correct polarity (+,-).  Refer
                                                               to NFPA Master/Combination Wiring Dia-
                                                               gram (Section 3.1/3.3).






















                 Figure 25:  B60 Board Wire Routing







                                                                   Figure 26: B1X Signal Board Wire Routing


                                                                     CAUTION:


                                                                Source equipment signal wires must be
                                                                connected to normally-closed, dry con-
                                                                tacts. No electrical voltage can be present
                                                                and contacts must be closed during normal
                                                                equipment operation. When contacts open,
                                                                an alarm condition will be activated.